Voltage Drop Calculator

Find the voltage drop on a copper or aluminum circuit, AC single-phase, three-phase or DC, and the smallest wire that keeps it within 3%.

Safety: This is an estimate for planning. Wire size is set by ampacity first (NEC 310.16), then voltage drop. Your local code and a licensed electrician have the final say.

Voltage drop — %
System
V
A
%

3% for a branch circuit or feeder; 5% total is the usual guide.

Drop
— V
Voltage at the load
— V
Resistance (Table 8, 75 °C)
— Ω / 1,000 ft
Power lost in the wire
— W
Longest run within your limit
— ft
Smallest size for your limit
—
Voltage drop diagram

Shopping list

    Quantities are rounded up to whole bags, blocks and pieces. Prices change by region, so add your own to see a total.

    How to use the voltage drop calculator

    Choose the system, enter the source voltage, the load current and the one-way length of the run, then pick the conductor material and size. The calculator gives the drop in volts and as a percentage of the source voltage, the voltage left at the load, the longest run that stays inside your limit, and the smallest wire size that would meet it.

    Voltage drop is only half of sizing a wire. The conductor must first be big enough to carry the current safely under NEC Table 310.16; the wire size calculator checks both at once.

    The formulas

    single-phase AC or DC: VD = 2 × L × I × R ÷ 1,000
    three-phase AC: VD = 1.732 × L × I × R ÷ 1,000
    percent drop = VD ÷ source voltage × 100

    L is the one-way length in feet, I the current in amps and R the conductor's resistance in ohms per 1,000 ft from NEC Chapter 9 Table 8. Single-phase and DC use 2 because current flows out and back; three-phase uses √3.

    Worked example: a 40 A, 240 V circuit, 100 ft of 8 AWG copper

    1. Table 8 resistance for stranded 8 AWG copper: 0.778 Ω per 1,000 ft.
    2. Drop: 2 × 100 × 40 × 0.778 ÷ 1,000 = 6.22 V.
    3. Percent: 6.22 ÷ 240 = 2.59%, inside the 3% guideline.
    4. The same run at 120 V would be 5.2%, which is why the circuit voltage matters as much as the wire.

    Resistance by size (NEC Table 8, stranded, 75 °C)

    AWGCopper Ω / 1,000 ftAluminum Ω / 1,000 ft
    143.14—
    121.983.25
    101.242.04
    80.7781.28
    60.4910.808
    40.3080.508
    20.1940.319
    1/00.1220.201
    4/00.06080.100

    Reducing voltage drop

    • Upsize the conductor. Each step of three AWG sizes roughly halves the resistance.
    • Raise the voltage. A 240 V circuit has half the current of the same load at 120 V, and a quarter of the percentage drop.
    • Shorten the run. Put a subpanel near distant loads.
    • Remember the equipment ground. When you upsize phase conductors for voltage drop, NEC 250.122(B) requires the equipment grounding conductor to be increased proportionally.

    Common mistakes

    • Using the round-trip length. Enter the one-way distance; the formula already doubles it.
    • Sizing for drop only. A big enough wire for voltage drop can still be too small for ampacity at short distances. Check both.
    • Ignoring start-up current. Motors draw several times their running current when starting, so drop is worse for a moment. Size motor circuits with that in mind.

    Questions people ask

    How do you calculate voltage drop?

    For single-phase AC and DC: VD = 2 × length × current × resistance per foot. For three-phase: VD = 1.732 × length × current × resistance per foot. Length is one way, in feet; resistance comes from NEC Chapter 9 Table 8 (ohms per 1,000 ft). A 100 ft run of 8 AWG copper carrying 40 A drops 2 × 100 × 40 × 0.778 ÷ 1,000 = 6.2 V.

    What is the maximum allowable voltage drop?

    Informational notes in NEC 210.19 and 215.2 recommend no more than 3% on a branch circuit or feeder and 5% overall from the service to the farthest outlet. They're recommendations, not requirements, but most designers follow them, and some equipment and local codes are stricter.

    Does voltage drop depend on the voltage?

    The drop in volts doesn't; it depends on current, length and wire. But the percentage does: 6 V is 5% of 120 V and only 2.5% of 240 V. That's why long runs are often wired at 240 V.

    Is aluminum wire worse for voltage drop?

    Aluminum has about 1.6 times the resistance of copper of the same gauge, so it drops more. An aluminum conductor is usually upsized by about two AWG sizes to match copper.

    How long can a wire run be before voltage drop is a problem?

    It depends on the load. At 120 V, 15 A on 14 AWG copper hits 3% at about 38 ft one way; 20 A on 12 AWG at about 45 ft. Above that, upsize the wire.

    Sources and assumptions

    Last reviewed 27 October 2026. Every formula on this page is checked against the worked example above in our automated tests. Found a problem? Tell us.