Conduit Fill Calculator

Find how many THHN/THWN wires fit in EMT, PVC Schedule 40 or 80, or rigid conduit, or check the fill for a mix of wire sizes, using the NEC Chapter 9 tables.

Safety: Conduit fill is only one limit. Ampacity derating for more than three current-carrying conductors (NEC 310.15(C)(1)), box fill and bending space also apply. Your local code and a licensed electrician have the final say.

Wires allowed — conductors
What do you want to know?
Conduit internal area (Table 4)
— in²
Wire area (Table 5)
— in²
Fill
— %
Allowed fill (Table 1)
— %
Same wire in every trade size
—
Wires allowed diagram

Shopping list

    Quantities are rounded up to whole bags, blocks and pieces. Prices change by region, so add your own to see a total.

    How to use the conduit fill calculator

    Pick the conduit type and trade size. In How many fit mode, choose a wire size and the calculator gives the maximum number of THHN/THWN-2 conductors allowed, following the method in NEC Annex C. In Check a mix mode, list up to three wire sizes with counts (include the grounding conductor) and it reports the percent fill against the limit for that number of wires.

    The method

    allowed area = conduit area (Table 4) × 53% (1 wire), 31% (2 wires) or 40% (3+ wires)
    max same-size wires = allowed area ÷ wire area (Table 5); round up if the decimal is 0.8 or more (Note 7)
    mixed wires: Σ wire areas ≤ allowed area

    Worked example: 12 AWG THHN in ¾ in EMT

    1. Table 4: ¾ in EMT has 0.533 in² inside, so 40% is 0.213 in².
    2. Table 5: one 12 AWG THHN is 0.0133 in².
    3. 0.213 ÷ 0.0133 = 16.0, so 16 conductors.

    Quick reference: THHN in EMT (40% fill)

    Wire½ in¾ in1 in1¼ in
    14 AWG12223561
    12 AWG9162645
    10 AWG5101628
    8 AWG36916
    6 AWG14712

    Calculated from Tables 1, 4 and 5 with Note 7, the same way NEC Annex C Table C.1 is built.

    Things that catch people out

    • Fill isn't derating. Twelve 12 AWG wires may fit in a conduit, but nine or more current-carrying conductors reduce each one's ampacity to 70% or less.
    • Different insulation, different areas. XHHW, THW and RHW are bigger or smaller than THHN; this calculator uses THHN/THWN-2 only.
    • Short nipples (24 in or less between boxes) may be filled to 60% (Chapter 9 Note 4).
    • Pulling is a separate question. A legal fill can still be a hard pull through several bends. Leave room for long runs.

    Questions people ask

    How many 12 gauge wires can go in 1/2 inch EMT?

    Nine 12 AWG THHN. NEC Table 4 gives ½ in EMT 0.122 in² at the 40% fill allowed for three or more wires, and Table 5 gives 12 AWG THHN 0.0133 in² each: 0.122 ÷ 0.0133 = 9.2, so 9.

    How many 12 gauge wires in 3/4 EMT?

    Sixteen 12 AWG THHN: 0.213 in² ÷ 0.0133 in² = 16.0.

    What is the 40% conduit fill rule?

    NEC Chapter 9 Table 1 limits conductors to 53% of the conduit's area for one wire, 31% for two wires, and 40% for three or more. The odd 31% for two wires exists because two round wires can jam against each other in a bend.

    What is Note 7 for conduit fill?

    When every conductor is the same size and the calculation leaves a decimal of 0.8 or more, Chapter 9 Note 7 lets you round up to the next whole number. For example, 8 AWG THHN in ¾ in EMT works out to 5.8, so 6 are allowed.

    Does the ground wire count toward conduit fill?

    Yes. Equipment grounding conductors count toward fill (Chapter 9 Note 3), even though they don't count as current-carrying for ampacity derating. Include them in the wire list.

    Sources and assumptions

    Last reviewed 27 October 2026. Every formula on this page is checked against the worked example above in our automated tests. Found a problem? Tell us.